DOI QR코드

DOI QR Code

A Study on Grounding Resistance Measurement of Power Supplying Substation using Grounding Current Division Factor and FOP Profile Method

접지전류 분류계수 및 전위강하곡선법을 이용한 운전 중인 변전소의 접지저항 측정 방법에 관한 연구

  • 안용호 (한국전력공사 전력연구원) ;
  • 최종기 (한국전력공사 전력연구원) ;
  • 김용학 (한국전력공사 전력연구원) ;
  • 한정열 (한국전력공사 전력연구원) ;
  • 이유진 (한국전력공사 전력연구원) ;
  • 한병성 (전북대학교 전자정보공학부)
  • Received : 2011.04.13
  • Accepted : 2011.05.06
  • Published : 2011.06.30

Abstract

Since transmission and distribution neutral wires are connected with a substation grounding grid, it is very difficult to measure grounding resistance of isolated substation grounding grid after the substation is energized. It is impractical to isolate the grounding grid from other parallel connections such as distribution line neutrals and overhead ground wires for grounding resistance measurement only. In this paper, we proposed and demonstrated a novel measurement method of grounding resistance of isolated substation grounding grid. For this method, grounding current division factor and conventional FOP(Fall-Of-Potential) profiles were measured at power supplying 154[kV] substation. The obtained FOP profile was processed with the measured grounding current division factor to produce the grounding resistance of isolated grounding grid. Simulated FOP profile agreed well with the measured one showing the validity of the proposed method.

Keywords

References

  1. 한국전력공사, “운전 중인 변전소의 접지계통 진단기술 개발연구(사후보고서)”, 2003.04.
  2. 최종기, 안용호, 정길조 “접지전류 측정에 의한 다중 접지계통의 접지저항 측정”, 전기학회논문지, 제53A권, 제4호, 2004. 4, pp.234-237.
  3. 한국전력공사, “운전 중인 변전소의 접지계통 진단기술 개발 연구”, 2002.03.
  4. 윤장완, 안용호, 정길조, 한병성 “지표면전위 해석에 의한 접지저항 측정기법에 관한 연구”, 한국조명.전기설비학회논문지, 제16권, 제4호, 2002. 7, pp.117- 123. https://doi.org/10.5207/JIEIE.2002.16.4.117
  5. Heppe, R. J., “Computation of potential at surface above an energized grid or other electrode, allowing for nonuniform current distribution,” IEEE Transactions on Power Apparatus and Systems, vol. PAS-98, no. 6, pp. 1978.1989, Nov./Dec. 1979. https://doi.org/10.1109/TPAS.1979.319377
  6. SES, RESAP Users' Manual, SES, 2000.
  7. SES, MALT Users' Manual, SES, 2000.