Surface Temperature Control of an Insulated Horizontal Pipe under Thermal Radiation Environment

복사효과를 포함하는 수평관 표면의 온도제어

  • 강병하 (국민대학교 기계시스템공학부) ;
  • 피창헌 (국민대학교 대학원) ;
  • 김석현 (국민대학교 기계시스템공학부)
  • Received : 2010.09.03
  • Accepted : 2010.12.02
  • Published : 2011.01.10

Abstract

Procedures for estimation of insulation thickness for a horizontal pipe for condensation control or personnel protection has been investigated, parallel to the previous work of a vertical wall case. Parameters include pipe diameter, emissivity, thermal conductivity, and operating temperatures. The results indicated that the surface emissivity plays a very important role in the design of insulation, specially for the case of high temperature application with low Bi. The effect of surface radiation in such case could be up to 65% of the total. Required insulation thickness for the surface temperature control increases as pipe diameter increases and as surface emissivity decreases. Adequate revision of specifications or standards to include newly invented insulation materials with high emissivity has been also suggested.

Keywords

References

  1. Mahlia, T. M. I., Taufiq, B. N., and Masjuki, H. H., 2007, Correlation between thermal conductivity and the thickness of selected insulation materials for building wall, Energy and Buildings, Vol. 39, No.2, pp. 182-187. https://doi.org/10.1016/j.enbuild.2006.06.002
  2. Bahadori, A. and Vuthaluru, H. B., 2010, A simple correlation for estimation of economic thickness of thermal insulation for process piping and equipment, Applied Thermal Engineering, Vol. 30, No. 2-3, pp. 254-259. https://doi.org/10.1016/j.applthermaleng.2009.08.010
  3. Sahin, A. Z. and Kalyon, M., 2005, Maintaining uniform surface temperature along pipes by insulation, Energy, Vol. 30, No.5, pp. 637-647. https://doi.org/10.1016/j.energy.2004.05.020
  4. Li, Y. F. and Chow, W. K, 2005, Optimum insulation-thickness for thermal and freezing protection, Applied Energy, Vol. 80, No.1, pp. 23-33. https://doi.org/10.1016/j.apenergy.2004.02.009
  5. Lee, H. K. and Kim, M. J., 1985, A study on thermal performance of external masonry wall structures by using foamed plastic as thermal insulation materials, Korean Journal of the Architectural Insitute of Korea, Vol. 5, No.2, pp. 267-270.
  6. Ahn, C. H. and Kong, S. H., 2007, A study on the interpretation of surface condensation depending on piping materials, Korean Journal of the Society of Living Environment System, Vol. 14, No.3, pp. 171-179.
  7. Yoon, K S. and Lee, K Y., 2008, A suitable thickness of flexible elastometic foam, Proceedings of the SAREK Winter Annual Conference, pp. 429-433.
  8. Oh, D. E., Park. J. I., Lee, M. W., Hong, J. K, Kang, B. H., and Kim, S. H., 2006, Effects of surface radiation on the insulation for mechanical system, Proceedings of the SAREK Summer Annual Conference, pp. 1006-1011.
  9. Cianfrini, C., Corcione, M. and Habib, E., 2006, Free convection heat transfer from a horizontal cylinder affected by a downstream parallel cylinder of different diameter, Int. J, Thermal Sciences, Vol. 45, pp. 923-931. https://doi.org/10.1016/j.ijthermalsci.2005.11.008
  10. Korean Standards, F2803, 2006, Standard practice for thermal insulation works.
  11. ASHRAE Handbook-Fundamentals, 2005, Insulation for mechanical system, Vol. 26, pp. 1-6, 26.

Cited by

  1. Analysis on Surface Temperature Control of an Insulated Vertical Wall Under Thermal Radiation Environment vol.24, pp.4, 2012, https://doi.org/10.6110/KJACR.2012.24.4.323