Horizontal Displacement Analysis of Electric Pole from Full Scale Pull-Out Test in Softground

연약지반에 시공된 전주의 실물인장실험을 통한 수평변위분석

  • 안태봉 (우송대학교 철도건설환경공학과)
  • Published : 2009.12.31

Abstract

Many electric poles in the softground have been collapsed due to external load such as typhoon wind load. In this study, the location, numbers and depths of acnchor blocks as well as depth of poles were varied to find horizontal displacement of poles through pull-out tests. The 10 types of tests were performed, and lateral displacements showed differences depending on location, numbers and depth of poles. The bending is generated in the upper part at the initial load, but it moved to central part as load increased. The maximum horizontal displacement decreased to 1/1.6 at -0.5[m] depth of anchor block and 1.3[m] additional laying depth of poles into ground. Two anchor blocks of poles are better than one acnchor block system, but one anchor block system is recommended because difference of displacement is not too large, and constructibilty is bad due to increase of excavation for anchor blocks.

연약지반상에 시공하는 수많은 전주가 태풍 등의 외부하중으로 전도파괴가 발생한다. 본 연구에서는 근가위치, 근가깊이, 근가개수, 전주근입깊이 등을 달리하며 연약지반에 실물크기의 전주에 인장실험을 실시하여 전주의 수평 변위분석을 실시하였다. 전주는 10개의 유형으로 나누어 실험한 결과 변위는 근가의 위치 및 수량, 전주기초의 근입깊이에 따라 뚜렷한 차이를 나타냈다. 초기하중 재하시 상부에서 굴절된 양상을 보이다 점증하중에 따라 전주의 중앙부로 굴절의 양상이 전이되었다. 근가위치는 G.L(-) 0.5[m]인 상태에서 전주기초 깊이 1.3[m]를 추가로 근입시 최대 수평변위는 약 1.6배의 감소를 보여 전주의 안정성이 증가하였다. 근가의 수는 근가 2개를 설치하는 것이 변위에 유리하나 큰 차이는 아니며 근가를 다수 설치하고 굴착면적이 커져 시공성이 떨어지는 단점이 있으므로 근가를 1개만 설치하여도 좋은 것으로 판단된다.

Keywords

References

  1. 손명윤 임종석, 점성토에 설치된 콘크리트 전주지반의 수평방향지지력, 대한토목학회 학술발표회, 2004
  2. 안태봉, 배전용 콘크리트전주 기초지반의 횡방향변위분석, 한국조명전기설비학회 논문집, Vol. 23, No.5 pp. 42-49, 2009
  3. White, D. J., Thompson, M. J., Suleiman,, M..T and Schaefer, V. R.. 'Behavior of Slender Piles Subject to Free-Field Lateral Soil Movement', Journal of Geotechnical and Geoenvironmental Engineering, Vol. 134, No. 4, pp. 428-436, April 2008 https://doi.org/10.1061/(ASCE)1090-0241(2008)134:4(428)
  4. Rajashree, S. S., Sitharam,T. G., 'Nonlinear Finite-Element Modeling of Batter Piles under Lateral Load',Journal of Geotechnical and Geoenvironmental Engineering, Vol. 127, No. 7, pp. 604-612, 2001 https://doi.org/10.1061/(ASCE)1090-0241(2001)127:7(604)
  5. Chen, S. L. and Chen, L. Z. 'Note on the Interaction Factor for Two Laterally Loaded Piles', Journal of Geotechnical and Geoenvironmental Engineering, Vol. 134, No. 11, pp. 1685-1690, 2008 https://doi.org/10.1061/(ASCE)1090-0241(2008)134:11(1685)
  6. 한국전력공사, '지반상태별 콘크리트전주 기초의 안전성 확보방안 최종보고서', 2004

Cited by

  1. Horizontal Stress Analysis of Electric Pole using Earth Pressure Cell from Mock-Up Tension Test vol.24, pp.8, 2010, https://doi.org/10.5207/JIEIE.2010.24.8.062
  2. Stress Analysis Acting on Electric Pole using Strain Gauge from Full Scale Pull-Out Test vol.24, pp.9, 2010, https://doi.org/10.5207/JIEIE.2010.24.9.049