Abstract
Because of the increase of power demand and expansion of downtown, it is necessary to install the power transformers at the substation in the residential area. But the public complaints have increased due to the noise of the power transformers in the substation. A soundproof wall has been employed to the power transformers in the outdoor substations and a soundproof door, a soundproof shutter and soundproof equipment for wind-path has been employed to power transformers in the indoor substations in order to isolate sound propagation from the noise of the power transformers. But the noise reduction results of these methods are not satisfied. In this study, a soundproof enclosure is developed to effectively isolate sound propagation from the noise of the power transformers. The performance of the sound attenuation of the developed soundproof enclosure is verified in a 154[kV] transformer. As a result, 15[dB] sound attenuation in 120[Hz] component is achieved by applying the developed soundproof enclosure to a 154[kV] transformer.
전력수요의 증가 및 도심지역의 확대로 도심지내 변전소에 전력용 변압기의 설치가 필요하나, 변전소의 전력용 변압기에서 발생하는 소음으로 인한 민원이 증가하고 있다. 따라서 전력용 변압기에서 발생하는 소음의 전파를 차단하기 위하여, 옥외 변전소의 전력용 변압기에는 방음벽을 적용하여 왔으며, 옥내 변전소에는 방음문, 방음 셔터 및 풍도형 방음장치 등을 적용하여 왔다. 그러나 이러한 방법에 의한 소음저감 효과는 만족할 정도에 이르지 못하는 실정이다. 본 연구에서는 전력용 변압기로부터 발생되는 소음을 효과적으로 차단하기 위해 변압기 차음실을 개발하였다. 개발한 변압기 차음실은 154[kV] 변압기에 적용하여 120[Hz] 성분에서 15[dB]의 소음저감 효과를 확인하였다.