A Comparative Study on the Electric Power Efficiency of IDCs with AC and DC Distribution Systems

교류배전시스템과 직류배전시스템이 적용된 IDC 전력효율 비교연구

  • Published : 2008.08.31

Abstract

Internet Data Centers (IDCs), which are resulted by the rapid progress of Information Technology industry, consist of high-density digital loads with internet server systems. Introduction of DC distribution system may simplify the conventional electric power conversion system, and may result in the improvement of electric power efficiency. However, this conjecture has never been tested under Korean IDC environment. In this study, electric power efficiency of DC distribution system from KT Namsuwon IDC is contrasted with that of conventional AC distribution system from KT Bundang IDC. DC 48[V] based distribution system showed 13.2[%] higher efficiency than the conventional AC based distribution system. The further analysis with the assumption of DC 380[V] suggests efficiency improvement over 25[%] can be achieved.

급격한 IT 산업 발전의 산물인 인터넷데이터센터(IDC)는 서버 시스템이 집적된 고밀도 디지털 부하로 구성되는 특징을 가지고 있다. IDC의 디지털 부하 특성을 고려하여 직류배전시스템을 도입하는 경우 전력 변환 체계의 단순화로 효율 향상의 가능성이 일부 제기되어 왔으나, 국내 IDC 환경에서의 효율성이 검증된 사례는 없었다. 본 논문에서는 교류배전방식을 적용한 KT 분당 IDC와 직류배전방식을 적용한 KT 남수원 IDC의 전력 효율을 비교 분석함으로써 국내 IDC 배전체계의 직류화에 따른 효율 개선 효과를 제시하였다. DC 48[V]를 배전하였을 때 직류배전 방식의 효율이 13.2[%] 높은 것으로 도출되었으며, DC 380[V]의 공급을 가정하였을 때에는 25[%] 이상의 효율 향상을 기대할 수 있었다.

Keywords

References

  1. 권원옥, 김성운, '저전력 데이터센터 기술 동향', 주간기술동향 1323호, pp.1-15, 2007.11.21
  2. My Ton, Brian Fortenbery, William Tschudi DC Power for Improved Data Center Efficiency, LBNL Reprot, Jan 2007
  3. William A Hammond, Efficient Power Consumption in the modern Dafacenter, Intel, March, 1, 2005
  4. 김재한, 양승욱, 목형수, 최규하, 손성용, 홍준희, '전력IT용 디지털 부하를 위한 저전압 직류급전시스템 연구', 전력전자학회, 전력전자학술대회논문집 pp.327-329, 2006.6
  5. 권원옥, 김성운, 김명준, '저전력 서버기술 동향', 주간기술동향 1306호, pp.1-10, 2007.7.25