Abstract
It is impossible to database(DB) the patterns of power cable events and cause analysis of faulted cable because the product liability(PL) law have been enforced in Korea, since 2002. In additions, simulation and pattern of power cable events are needed for DB system under accelerated deterioration. In this paper, we tested for resistance to cracking of cable below the 22.9[kV] class due to thermal stresses. This method of exam is following IEC 60811-3-1(Common test methods for insulating and sheathing materials of electric cables). From the results, The 22.9[kV] class A power cable was discolored on the surface and significantly reduced in the longitudinal direction. As the thermal weight properties of A power cable was definitely varied, we are able to guess the problem of manufacture. If the cable was defect by the manufacture, the victims would be able to claim for damage in the PL system.
2002년부터 시행되어오고 있는 제조물 책임법에 의해 사고케이블의 원인분석과 사고패턴에 대한 데이터베이스화가 중요하다. 더욱이 가속열화상태에서 전력케이블 사고의 패턴 및 모의실험은 데이터베이스 시스템 구축에 필요하다. 본 논문에서는 열 열화 따른 22.9[kV]이하 케이블의 열 충격시험을 수행하였다. 이 시험은 IEC60811-3-1에 따른다. 시험결과로부터, 22.9[kV]급 A사 전력케이블은 표면이 변색되었고 길이방향으로 급격하게 감소되었다. 특히, A사 전력케이블의 열 중량 특성이 심하게 변함에 따라, 케이블 제조상의 문제일 것이라 추측된다. 만약 전력케이블의 제조상의 결함에 의한 것이라면, 피해자들은 PL환경 하에 손해배상을 받을 수 있을 것이다.