A Study on the Performance and Dehumidification Load of an HVAC System for Conservation of Ancient Tombs

고분 공조시스템의 운전특성 및 제습부하에 관한 연구

  • Park, Jin-Yang (Graduate School, Kongju National University) ;
  • Ko, Seok-Bo (Graduate School, Kongju National University) ;
  • Jun, Hee-Ho (Graduate School, Kongju National University) ;
  • Jun, Yong-Du (Department of Mechanical and Automotive Engineering, Kongju National University) ;
  • Lee, Kum-Bae (Department of Mechanical and Automotive Engineering, Kongju National University)
  • 박진양 (공주대학교 기계공학과 대학원) ;
  • 고석보 (공주대학교 기계공학과 대학원) ;
  • 전희호 (공주대학교 기계공학과 대학원) ;
  • 전용두 (공주대학교 기계자동차공학부) ;
  • 이금배 (공주대학교 기계자동차공학부)
  • Published : 2007.03.10

Abstract

Although the importance of good conservation of historical sites including ancient royal tombs is well aware, still not much attention has been paid for facilities to realize it. There are numerous ancient royal tombs spread in Korean peninsula which are opened and some of them are selectively on display for public access. However, the conservation measures of these sites have not been seriously investigated. Even the level of understanding of the underground environment of tombs is not satisfactory. In the present study, we focus on the dehumidification loads to maintain appropriate conservation conditions in terms of temperature and humidity. Two experimental tombs different in size were built in KNU (Kongju National University) campus with the dimensions ($L{\times}W{\times}H$) of $1.0m{\times}2.8m{\times}1.0m\;and\;1.3m{\times}3.0m{\time}1.2m$, respectively, HVAC systems are installed to maintain a suitable condition for conservation, i.e., $22{\pm}2^{\circ}C$ in temperature and $55{\pm}5%$ in relative humidity. The condensed water are measured to estimate the dehumidification loads while the temperature and the humidity inside the tombs were maintained within the specified range.

Keywords

References

  1. Kim, J. Y. and Oh, M. D., 2002, Study on the performance of humidity control of the air-tightened exhibition showcase in the museum, SAREK 2002 Summer Annual Conference, pp. 496-501
  2. Thomson, G., 1986, The Museum Environment, 2nd ed., Butterworth-Heinemann, London, p.88
  3. Lee, J. K. and Song, T. H., 1999, Experimental investigation of dew formation and heat transfer in the original upper structure of Sokkuram grotto, SAREK 1999 Summer Annual Conference, pp.68-76
  4. Lim, K. H., Jeong, S. U., Lim, Y. G., Kong, S. H., Moon, S. H. and Yoon, H. K., 1998, An experimental study on the Sokkuram cave temple dome's indoor environment of miniature model in winter season, SAREK 1998 Summer Annual Conference, pp.187-190
  5. Suh, M. C., Lee, N. S., Choi, S. W., Kim, G. H., Jeong, S. M. and Lee, K. B., 1998, In-situ status and conservational strategy of the Muryong royal tomb, the Songsanri tomb No.5 and the Songsanri tomb No.6 of Baekje dynasty, The Research Institute of Bas. Sci. Kongju Nat'l. Univ., The Journal of Natural Science, Vol. 7, pp.147-161
  6. Jun, Y. D., Lee, K. B., Kim, H. G. and Ko, S. B., 2004, Temperature and humidity distribution inside Sinkwan-ri tomb, SAREK 2004 Winter Annual Conference, pp.601-607
  7. SAREK, 2001, SAREK Handbook, Vol. 2, Air-Conditioning, pp. 1.3-1.4
  8. Korea Meteorological Administration, 2001, Climatological normals of Korea
  9. Lee, K. B., 2005, Development of an Optimized HVAC System for Ancient Tombs Conservation, 3th ed., Kongju Nat'l. Univ., pp. 141-156