A Study on Application of Distributor for Duct Design at House Ventilation System

주택용 환기시스템의 덕트설계를 위한 분배기 적용성 검토

  • Yee, Jurng-Jae (Faculty of Architectural Engineering and Design, Dong-A Univ.) ;
  • Choi, Seok-Yong (Graduate School of Architectural Engineering Studies, Dong-A Univ.) ;
  • Kim, Seok-Keun (Graduate School of Architectural Engineering Studies, Dong-A Univ.) ;
  • Kim, Kwang-Hyun (Graduate School of Architectural Engineering Studies, Dong-A Univ.) ;
  • Lee, Young-Woo (Gomotec Corporation) ;
  • Kim, Hwan-Yong (Faculty of Architectural Engineering and Design, Gyoungsang Univ.)
  • Published : 2007.11.10

Abstract

Although these days application of heat recovery ventilation and improved kitchen ventilation system came into wide use in mixed-use residential buildings and exclusive residences, there are not enough ventilation systems except the local ventilation of kitchens and rest rooms. It is very important part to regulate and distribute correct air flow rate for controlling air change rate. The purpose of this study is to investigate the application of distributor at house ventilation system by comparing a duct system with out distributor and with distributor. The results of this study are as follows. (1) When using distributor though the size of duct diameter is reduced rapidly, the pressure loss doesn't rise largely. The pressure loss without distributor is 4.08 mmAq, the pressure loss with distributor 4.10 mmAq. (2) To use distributor can reduce materials of duct and secure enough ceiling space by reducing duct diameter. (3) Diameters and air flow paths of distributor on the design stage are important part for accurate air flow rate.

Keywords

References

  1. Moon, J. S., Kang, S. Y., Lee, S. C., Yoo, H. S., and Lee, J. H., 2004, Analysis of air flow rate distribution for the bathroom exhaust system in high-rise buildings using t-method, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 16, No.3, pp. 265-272
  2. Yee, J.J, Joo, S. Y., Kim, K. H., and Choi, S. Y., 2006, The comparative experiment of Duct design method with equal friction loss method and t-method on a house ventilation system, Proceedings of the SAREK 2006 Summer Annual Conference, pp. 99- 104
  3. Yee, J.J. and Choi, S. Y., 2006, A pressure loss experiment and examination of t-method's application propriety for duct design of house ventilation system, Journal of The Architectural Institute of Korea, Vol. 22, No. 10, pp.353-362
  4. SMACNA, 1985, HVAC Construction Standards- Metal and Flexible, SMACNA
  5. SMACNA, 1990, Duct Design Committee, HVAC Systems Duct Design, SMACNA
  6. ASHRAE, 1997, ASHRAE Handbook, Fundamentals, Chapter 32. Duct Design