Abstract
In this study, we presented the problems in the insulation cover of 22.9kV transformer bushing through investigating actual conditions. After thermal stress applied to the insulation cover, deterioration patterns, thermogravimetric and infrared characteristics were analyzed, and the results were applied to the cause analysis of accidents and judgement of safety. The insulation covers are used to protect exposed terminals of transformer, but they had improper size and length. Therefore, they could not show efficient insulation function. In case that thermal stress of $150^{\circ}C$ was applied to the insulation covers, plastic insulation covers(A, B, D, E) damaged severely, whereas rubber insulation cover(C) showed normal shapes. In the result of thermogravimetric analysis, the thermal gravity of plastic covers(A) decreased about 33.3% at $307.8^{\circ}C\;to\;405.9^{\circ}C$. and he thermal gravity of rubber covers (C) decreased about 53.7% at $258.8^{\circ}C\;to\;32.9^{\circ}C$. In the result of FT-IR analysis, plastic covers showed peaks characteristic of $CH_2,\;CH_3$, C=O and C=C bonds, whereas rubber covers showed peaks characteristic of OH, $CH_2,\;CH_3$, C=O, C=N and C=C bonds.
본 논문에서는 22.9 kV용 변압기 부싱 절연 커버의 실태조사를 실시하였다. 절연 커버에 열적 스트레스를 인가하여 열화 패턴, 열 중량 변화, 적외선 특성 등을 해석하여 전기사고 원인 분석을 위한 근거를 제시하고자 한다. 노출된 변압기 단자를 보호하기 위해 설치한 절연 커버의 크기 및 길이가 부적절한 것이 확인되었다. 절연 커버에 $150^{\circ}C$의 열적 스트레스를 인가한 경우 플라스틱 절연 커버(A, B, D, E)는 심한 변형이 일어났으나, 고무 절연 커버 C는 정상이었다. 열 중량 분석 결과 절연 커버 A는 $307.8{\sim}405.9^{\circ}C$에서 33.3%의 감소가 있었으며, 절연 커버 C는 $258.8{\sim}332.9^{\circ}C$에서 53.7%의 감소가 발생하였다. FT-IR 분석에서 플라스틱 절연 커버는 $CH_2,\;CH_3$, C=O, C=C 결합 구조를 갖는 것으로 나타났으며, 고무 절연 커버는 OH, $CH_2,\;CH_3$, C=O, C=N, C=C 등의 결합인 것을 알 수 있었다.