DOI QR코드

DOI QR Code

Feature Extraction of Simulated fault Signals in Stator Windings of a High Voltage Motor and Classification of Faulty Signals

  • Park, Jae-Jun (Department of Electrical Electronic Engineering, Joongbu University) ;
  • Jang, In-Bum (Department of Electrical Engineering, Kwangwoon University)
  • Published : 2005.10.01

Abstract

In the case of the fault in stator windings of a high voltage motor. it facilitates certain destructive characteristics in insulations. This will result in a decreased reliability in power supplies and will prevent the generation of electricity, which will result in huge economic losses. This study simulates motor windings using normal windings and four faulty windings for an actual fault in stator winding of a high voltage motor. The partial discharge signals produced in each faulty winding were measured using an 80 PF epoxy/mica coupler sensor. In order to quantified signal waves its a way of feature extraction for each faulty signal, the signal wave of winding was quantified to measure the degree of skewness shape and kurtosis, which are both types of statistical parameters, using a discrete wavelet transformation method for each faulty type. Wave types present different types lot each faulty type, and the skewness and kurtosis also present different quantified values. The result of feature extraction was used as a preprocessing stage to identify a certain fault in stater windings. It is evident that the type of faulty signals can be classified from the test results using faulty signals that were randomly selected from the signal, which was not applied in the training after the training and learning period, by applying it to a back-propagation algorithm due to the supervising and learning method in a neural network in order to classify the faulty type. This becomes an important basis for studying diagnosis methods using the classification of faulty signals with a feature extraction algorithm, which can diagnose the fault of stator windings in the future.

Keywords

References

  1. Y.-J. Kim, D.-H. Hwang, B.-C. Shin, D.-Y. Park, and J.-W. Kim, 'Development of continuous partial discharge monitoring system for generator stator insulations', Conference Record of the 2000 IEEE International Symposium on Electrical Insulation, Anaheim, CA USA, p. 5, 2000
  2. G. C. Stone and H. G. Sedding, 'In-service evaluation of motor and generator stator winding using partial discharge tests', IEEE Trans, on Industry Applications, Vol. 31, No. 2, p. 299, 1995
  3. J. P. Zondervan, E. Gulski, and J. J. Smit, 'Fundamental aspects of PD patterns of on-line measurements on turbogenerators', IEEE Transactions on Dielectrics and Electrical Insulation, Vol. 7, No. 1, p. 59, 2000
  4. G. Stone, 'Importance of bandwidth in PD measurement in operating motors and generators', IEEE Trans, on Dielectrics and Electrical Insulation, Vol. 7, No. 1, p.6, 2000
  5. J.-J. Park, D.-J. Kwon, Y.-C. Song, and C.-B. Ahn, 'A study on feature extraction of transformers aging signal using discrete wavelet transform technique', Trans. KIEE, Vol. 50C, No. 3, p. 121, 2001
  6. J.-J. Park and Y.-C. Song, 'A study on diagnosis of transformers aging state using wavelet transform and neural network', J. of KIEEME(in Korean), Vol. 14, No. 1, p. 84, 2001
  7. G. J. Paoletti and A. Golubev, 'Partial discharge theory and technologies related to medium-voltage electrical equipment', IEEE Application, Vol. 37, No. 37, p. 90, 2000
  8. T. Brosche, W. Hiller, and E. Fauser, 'Novel characteristic of PD real-time measurement of pulse parameters', IEEE Trans. Electrical Insulation, Vol. 6, No. 1, p. 51, 1999
  9. W. Wang, K. Tan, K. Gao, and W. Gao, 'Optimal Feature Extraction for Partial Discharge Recognition', Project(No. 5963 7200)supported by NSFC and NEEPC, p. 115, 2000.
  10. K. Gao, K. Tan, and F. Li, 'PD pattern recognition for stator bar models with six kinds of characteristic vecotors using BP network', IEEE Trans, on Dielectrics and Electrical Insulation, Vol. 9, No. 3, p. 381, 2002.