온도측정에 의한 산화아연형 피뢰기 진단

ZnO Arrester Diagnosis by Measurement of Temperature

  • 길경석 (한국해양대학교 전기전자공학부) ;
  • 한주섭 (한국해양대학교 산업기술연구소) ;
  • 송재용 (한국해양대학교 전기전자공학부) ;
  • 서황동 (한국해양대학교 전기전자공학부) ;
  • 문승보 (한국해양대학교 전기전자공학부) ;
  • 박태곤 (창원대학교 매카트로닉스공학부)
  • 발행 : 2005.08.01

초록

In this paper, surface temperatures of ZnO arresters as a function of ambient temperatures and leakage currents were experimentally investigated. The variations of the leakage current was below 10 uA, which comes about $4.5\%$ of the normal leakage current. Temperature differences between the ambient and the surface of arresters were not shown until $150\%$ to the normal leakage current, and were remarkable over $200\%$. From the results, we deduced a couple of polynomials which enables the calculation of the leakage current by the measurement of surface temperature. Tests on used arresters have shown the same results as the experimental one. Also, we expect that an arrester diagnosis is possible by measuring the surface temperature of them after more studies on the effect of wind, moisture penetration, and arrester types.

키워드

참고문헌

  1. D. R. Clarke, 'Varistor Ceramics', Journal of American Ceramic Society, vol. 82, no. 3, pp. 485-502, March 1999 https://doi.org/10.1111/j.1151-2916.1999.tb01793.x
  2. T. K. Gupta, W. G. Carlson and P. L. Hower, 'Current Instability Phenomena in ZnO Varistors', Journal of Applied Physics, vol. 52, no. 6, pp. 4104-4111, 1981 https://doi.org/10.1063/1.329262
  3. K. Eda, A. Iga and M. Matsuoka, 'Degradation Mechanism of Non-ohmic Zinc Oxide Ceramics', Journal of Applied Physics, vol. 51, no. 5, pp. 2678-2684, August 1980 https://doi.org/10.1063/1.327927
  4. J. Lundquist, L. Stenstrom, A. Schei, B. Hansen, 'New Method for Measurement of the Resistive Leakage Currents of Metal-Oxide Surge Arresters in Service', IEEE Transaction on Power Delivery, vol. 5, no. 4, pp. 1811-1822, November 1990 https://doi.org/10.1109/61.103677
  5. S. Shirakawa, F. Endo, H. Kitajima, S. Kobayashi, K. Kurita, K. Goto, M. Sakai, 'Maintenance of Surge Arrester by a Portable Arrester Leakage Current Detector', IEEE Transaction on Power Delivery, vol. 3, no. 3, pp. 998-1003, July 1988 https://doi.org/10.1109/61.193879
  6. O. Nigol, 'Methods for Analyzing the Performance of Gapless Metal Oxide Surge Arresters', IEEE Transaction on Power Delivery, vol. 7, no. 3, pp. 1256-1262, July 1992 https://doi.org/10.1109/61.141839
  7. 길경석, 한주섭, 주문노, '누설전류측정에 의한 피뢰기 열화진단에 있어 전원고조파의 영향', 대한전기학회 논문지, 1호, 제 53C권, pp. 41-46, 2003. 1.
  8. S.N. Fernando, M.R. Raghuveer, 'Technique to Examine the Influence of Voltage Harmonics on Leakage Current Based MOSA Diagnostic Indicator', Proceedings of 2000 IEEE Conference on Electrical Insulation and Dielectric Phenomena, vol.2, pp. 596-599, October 2000 https://doi.org/10.1109/CEIDP.2000.884030
  9. S. Tominaga, Y. Shibuya, Y. Fujiwara, M. Imataki, T. Nitta, 'Stability and Long Term Degradation of Metal Oxide Surge Arresters', IEEE Transaction on Power Apparatus and Systems, vol. PAS-99, no. 4, pp. 1548-1556, July/August 1980 https://doi.org/10.1109/TPAS.1980.319580