Abstract
A test program was conducted on full-scale steel moment connections constructed using a T-stiffener. In the T-stiffener connection, the beam-to-column connection was reinforced with the horizontal and vertical element of the T-stiffener to resist moment under severe cyclic loads. A total of five specimens were tested in this study together with a concrete-filled tubular(CFT) column(${\sqsubset}-500{\times}500{\times}12$) and a steel beam($H-506{\times}201{\times}11{\times}19$). For the specimens, the T-stiffener was combined with RBS (also known as "Dog-bone") detail or Horizontal Element Hole(HEH) detail constructed to enhance deformation capacity. The test program showed excellent seismic performance for specimens constructed with an RBS or an HEH. except the specimens had brittle failure of VE. The test results also showed that the connections all developed maximum moments at the face of the column. Such moments were at least 15% and as much as 36% larger than the plastic moment capacity of the beam. based on the actual yield stress of the beam steel.
T-스티프너로 보강한 모멘트 접합부의 실대형 실험이 수행되었다. 극심한 반복하중하에서 접합부의 변형모멘트 저항능력을 높이기 위해서 T-스티프너의 수직 및 수평요소로 보강하였다. 본 연구에서는 모두 5개의 실험체에 대한 실험을 수행하였는데, 접합부를 구성함에 있어서 CFT기둥 (${\boxe}-500{\times}500{\times}12$)과 H형강보 ($H-506{\times}201{\times}11{\times}19$)를 사용하였다. 접합부의 변형능력을 향상시키기 위해 RBS 상세(Dog-bone)와 수평요소 홀(HEH) 상세를 조합했다. 실험결과 RBS와 HEH 상세를 가진 실험체는, VE가 취성파단한 실험체를 제외하면, 모두 우수한 내진성능을 보였다. 또한, 모든 접합부의 최대내력은, 보의 실제의 항복하중을 사용한 값으로 구한 전소성모멘트를 적어도 15%에서 많게는 36%정도로 상회하였다.