DOI QR코드

DOI QR Code

The development of LVI tester for application of transformers winding deformation diagnosis

변압기 권선변형 진단에 적용하기 위한 LVI 시험기 개발

  • Published : 2002.09.01

Abstract

The assessment of the condition of a transformer winding which is suspected of having suffered short circuit damage can be difficult. Conventional test such as winding resistance, magnetic current or insulation resistance will only detect damage if a permanent electrical fault exists. Visual inspection of windings necessitates the removal of oil and in many cases only a very small proportion of the winding can be seen. We describe the characteristic of LVI test system and methods to detect the deformation of windings in the power transformers. As the front rise time of recurrent-surge generator pulse less than 1000 ㎱ and the peak value of pulse is about 500 V, we have the good results of detecting winding deformation in the LVI test of transformers.

본 논문은 LVI 시험기를 개발하여 모델 변압기 및 유입식 변압기에 적용해 LVI 시험 분석기술을 개발하였다. LVI시험기는 본체, 터미널 박스 및 케이블로 구성하였고, ANSI규격에서 요구하는 출력특성을 갖도록 설계 제작하였다. 모델 변압기는 탭들을 만들어 변압기의 권선변형 모델을 만들 수 있도록 하였고, 유입식 변압기는 실제 현장에서 사용되는 3상 변압기이다. LVI 시험기는 펄스폭이 1000 ㎱ 이하의 파두 시간과 펄스 최대 전압 500 V로 제작되었다. LVI 시험기로써 실험을 실시하여 성능을 평가한 결과 측정된 파형 분석으로 권선의 축방향과 반경방향으로의 움직임을 구별할 수 있어 변압기 예방 진단에도 효과가 기대된다.

Keywords

References

  1. A.C. Hall and P.G Parrott "Experience with the low voltage impulse testing of power transformers."
  2. R.E. Ayers "Low-voltage impulse testing of transformer."
  3. E.P. Dick and C.C. Erven Transformer diagnostic testing by frequency response analysis", IEEE paper F78 024-2.
  4. W. Lech and L. Tyminski," Detecting Transformer winding Damage. The Low Voltage Impulse Method", Electrical Review Vol. 179, No.21, pp. 768-772, 1966.
  5. R. A. Smith and M. Waters, "Detection of winding Damage in Power Transformers using the Low Voltage Impulse Method.", ERA Report No. 5252, 1969.
  6. E. J. Rogers and L. E. Humbard,"Low Voltage Impulse Testing of Power Transformers." IEEE Paper No.71, TP 535-PWR., pp. 1281-1293, 1971.
  7. "IEEE Guide for Short-Circuit Testing of Distribution and Power Transformers" Part II IEEE C57. pp. 61-75, 1993.
  8. 조 국희, 강 동식, 김 광화, 권 동진, "변압기 권선변형 L.V.I. 진단 실적용을 위한 연구", 대한전기학회 하계학술대회, DHP-12, pp. 1638-1640, 1998.