Abstract

An on-line ultrasonic detector was developed to continuously monitor the ultrasonic signal due to partial discharge in transformer in service. The on-line ultrasonic detector has a band-pass filter designed to measure only the frequencies from 50 to 300[㎑] of ultrasonic signal, to remove electrical and mechanical noises from outside of the transformer, and tlle ultrasonic sensor contains a pre-amplifier with 60[dB] gain. The ultrasonic signal discrimination algorithm which discriminates the ultrasonic signal duration was developed to remove the ultrasonic signal due to OLTC operation having similar characteristics to those due to partial discharge. The reliability of the on-line ultrasonic detector developed in this study was convinced of measurement the ultrasonic signals from the model. transformer in laboratory and transformer in service.

운전중인 변압기 내부의 부분방전에 의한 초음파 신호를 상시 감시하기 위한 초음파 상시 측정장치를 개발하였다. 초음파 상시 측정장치는 변압기 외부에서 발생하는 전기적 및 기계적인 노이즈를 제거하고 변압기 내부의 부분방전에 의한 초음파 신호만을 측정하기 위하여 50~300[KHz] 주파수 대역만 집중 측정하도록 협대역 필터를 설계하였으며, 초음파 센서는 60[dB] 증폭도의 프리앰프 내장형으로 개발하였다. 부분방전에 의한 초음파 신호와 특성이 유사한 부하시 탭 절환장치의 동작에 의한 초음파 신호를 제거하기 위하여, 초음파 신호의 지속시간으로 판별하는 초음파 신호판별 알고리즘을 개발하였다. 본 연구에서 개발한 초음파 상시 측정장치는 실험실의 모의 변압기와 현장에서 운전중인 변압기에서 부분방전에 의한 초음파 신호를 측정하여 신뢰성을 확인하였다.

Keywords

References

  1. D.J. Kweon et al., “Development of the preventive diagnostic system for the 765kV substation equipments,” KEPRI Final Report, pp.1-128, 2001.
  2. “變壓器の豫防診斷の技術とその現狀動向,” 日本電氣學會技術報告, II 部 弟344號, pp.32-33, 1990.
  3. User's Manual of the TNU and Hydran 201i, Syprotec, pp.1-48, 1999.
  4. E. Lemke, “User's manual of the partial discharge measuring system LDS-6,” LEMKE Diagnostics GmbH, pp.5-79, 2000.
  5. User's manual of the OLTC monitoring system, MR, 1999.
  6. H. Kaward et. al., “Partial discharge automatic monitor for oil-filled power transformer,” IEEE Trans. PAS, Vol.103, No.2, pp.422-428, 1984. https://doi.org/10.1109/TPAS.1984.318261
  7. D.J. Kweon, “An application of the on line partial discharge measurement method in transformer,” The Korea Institute of Electrical Engineers, Vol.50C, No.8, pp.394-400, 2001.
  8. D.J. Kweon et al., “A study on feature extraction of transformers aging signal using discrete wavelet transform technique,” The Korea Institute of Electrical Engineers, Vol.50C, No.3, pp.121-129, 2001.
  9. D.J. Kweon et al., “A study on the transformer diagnostic technique using ultrasonic sensor,” The Korea Institute of Illuminating and Electrical Insulation Engineers, Vol.8, No.2, pp.46-53, 1994.
  10. D.J. Kweon, H.R. Kwak, “A study on the detection of ultrasonic signal for the diagnosis of transformer,” The Korea Institute of Illuminating and Electrical Insulation Engineers, Vol.9, No.6, pp.65-70, 1995.
  11. User's manual, “Mistras 2001 AEDSP32/16,” Physical Acoustics Corporation, pp.1-96, 1996.
  12. Catalog, “Acoustic emission detector,” NF Corporation, pp.1-38, 1998.
  13. D.J. Kweon et al., “Ultrasonic noises in power transformer,” Proceedings of the KIEE Summer Annual Conference, pp.2305-2307, 1999.
  14. D.J. Kweon et al., “Ultrasonic frequency spectrum of partial discharge in transformer and outside corona,” Proceedings of the KIEE Spring Annual Conference, pp.270-272, 1999.