수중 빙 제조방식을 적용한 빙축열시스템의 축방냉 특성 실험

Experiment of Characteristic on the Charge and Discharge of Cold in Ice Storage System Applied Ice Making Method In-Water

  • 발행 : 2002.01.01

초록

This paper is concerned with the development of a new method for making and separating ice and saving floated ice by installing an evaporation plate at in-water within a storage tank. In a conventional harvest-type ice storage system, a tank saves ice by separating a formed ice from an installed evaporation plate, which is located above an ice storage tank as an ice storage system. A new harvest-type method shows very good heat transfer efficiency than a convectional method. It is because the evaporation panel is directly contacted with water in a storage tank. Also, at a conventional system a circulating pump, a circulating water distributor and a piping are installed, but these components are not necessary in a new method. In this study two kinds of ice storage systems are experimentally investigated to study the thermal characteristics of ice storage tanks. The results showed discharge of cold capacity of new type indicated the high values about 30~40% based on five time of drive, the temperature difference of inlet/outlet occurred the big range about $1.3^{\circ}C$. So, the new type which makes ice in water showed superiorly.

키워드

참고문헌

  1. Proceedings of the SAREK Summer Annual Conference (II) Characteristics of electric power demand and promotion of the distribution of ice storage cooling system Jang, M. C.
  2. Proceedings of the SAREK Summer Annual Conference (II) Mini-thermal storage air conditioning Cho, H. G.
  3. Korean Journal of Air-Conditioning and Refrigeration Engineering v.11 no.1 Prediction of practically chargeable cold energy in an ice storage system Lee, D. Y.(et al.)
  4. The Korea Society for Energy Engineering v.9 no.4 Experiments on the Characteristic of Storage Tank in In-Water Harvest-Type Ice Storage System Kim, J. D.(et al.)
  5. Journal of Heat Transfer v.98 Transient Natural Convection of Water in a Horizontal Pipe With Constant Cooling Rate Through 4℃ Cheng, K. C.;Takeuchi, M. https://doi.org/10.1115/1.3450604
  6. Transactions of the Korean Society of Mechanical Engineers v.25 no.5 Experiments on Operation Characteristics of In-Water Harvest-Type Ice Storage System Choi, I. S.(et al.)
  7. Korean Journal of Air-Conditioning and Refrigeration Engineering v.8 no.4 A Study on Two Phase Heat Exchange of Plate Type PCM Container Kim, H. S.(et al.)
  8. Proceedings of the SAREK Winter Annual Conference(II) Characteristics Experiment of Under Water-Harvest-Type Ice Storage System Park, C. G.(et al.)
  9. International Journal of HVAC&R Research v.3 no.2 A simulation environment for the analysis of ice storage controls Carey, C. W.;Mitchell, J. W.;Brandemuehl, M. J. https://doi.org/10.1080/10789669.1997.10391367