Abstract
The problem of the flocculation basin was induced by installing the pilot plant using tracer test at Yang-Duck water treatment plant in Pohang cite. The flocculation basin model downscaled as 1/20 was made of acryl and evaluated hydraulically by transforming the section of the effluent in the flocculation basin. The optimum section of the effluent was suggested and applied to the plant. The efficiency of the flocculation basin according to improvement was evaluated by the particle counter which can count the number of particles each size fraction. The results of this study are as follows : First, it was desirable to make the retention time as short as possible because the flow and the index value were similar regardless of the retention time. Second, after the modification in Yang-Duck water treatment plant, the problem of destruction of floe was improved and the plant was operated satisfactorily. The hydraulic experiment with tracer test can be applied to the performance evaluation as well as improvement of facility in unit process of existing water treatment plant. Additionally, it can be used to find a design factor in the new water treatment plant.
본 연구에서는 포항시 양덕정수장에 tracer test를 이용한 pilot plant를 설치하여 기존 플록형성지에 대한 문제점을 도출하였다. 또한 플록형성지 각단 유출부의 단면을 여러 가지 형태로 변경시키면서 수리학적 평가를 실시하였고, 그 결과 플록형성지의 각단 유출부에 대한 최적 개량단면을 제시하였고, plant에 적용하여 현재 운전중에 있다. 또한 입자의 크기별 개수를 측정할 수 있는 particle counter를 이용하여 플록형성지 개량후의 효율을 평가하여 다음과 같은 결론을 얻었다. 체류시간에 관계없이 전체적으로 비슷한 흐름과 index 수치를 나타내므로 체류시간을 가능한 짧게 잡는 것이 바람직하다고 판단된다. 또한 양덕정수장의 플록형성지 개선공사후 기존의 플록이 깨어지는 문제가 개선되어 상당히 양호하게 운전되고있으며, tracer test를 이용한 수리학적 특성 실험방법은 플록지형성지 뿐만 아니라 기존 정수장의 단위공정에 대한 성능평가나 시설개선에 사용할 수 있으며, 신설정수정의 설계인자를 구하는데 유용하게 이용할 수 있다.