Abstract
This paper represents the control algorithm of the instantaneous voltage sag corrector for the power quality enhancement in distribution line. Especially, a novel detection technique of the symmetrical components is proposed for the analysis of the three-phase unbalanced and asymmetrical problems caused by the single line ground fault which is he most frequent event. This proposed method is based on the simple calculation and the control references of the symmetrical components for voltage compensation can be described as dc value without any other phase detection procedure. And also, for the generation of the reference voltages, the UF and MF defined by IEC is considered. Using this proposed control algorithm, the compensator has the fast dynamic characteristics and the THD of the compensated voltage waveform is very low. Finally, the validity of the proposed algorithm is proved by the PSCAD/EMTDC simulation and experimental results.
본 논문은 배전계통의 전력품질 개선을 위한 순시 전압강하 보상기의 제어 알고리즘에 대한 연구를 수행하였다. 특별히 순시적인 전압강하의 원인중 가장 대표적인 1선 지락사고 시에 발생하는 불평형과 비대칭 문제를 해석하기 위하여 새로운 대칭성분 검출 기법을 제안하였다. 제안되 방법은 간단한 연산만을 사용하며, 전압보상을 위한 대칭성분의 제어 기준값이 별도의 위상검출 과정을 거치지 않고도 직류 값으로 표현되도록 하였다. 그리고 기준전압의 발생 시에 IEC에서 규정하고 있는 UF와 MF를 사용하도록 하였다. 제안된 제어기법을 사용하면 보상장치는 매우 빠른 응답특성을 가지고 보상된 전압 파형의 총고조파왜형률(THD)도 매우 낮게 된다. 마지막으로 EMTDC 시뮬레이션과 실험을 통하여 제안된 방법의 타당성을 입증하였다.