A Study on the Heat Transfer Reduction due to the Clinker in the Thermal Poorer Plant

화력발전소에서 용융회가 열전달 감소에 미치는 영향에 관한 연구

  • 강희찬 (군산대학교 기계공학부) ;
  • 이규욱 (서천화력발전처 품질관리과)
  • Published : 2000.02.28

Abstract

This study was conducted for the heat transfer reduction due to the clinker formed in the furnace of the thermal power plant. The thermal properties of clinker such as thermal conductivity, specific heat, density and void fraction were measured. The thermal conductivities of the clinker were ranged $0.32-0.54W/m{\cdot}K$ and the average specific heat and the void fraction were $930J/kg{\cdot}K$ and 0.36 respectively. The thermal resistance of clinker was the greatest among the thermal resistances. It was found that the clinker reduces more than 90% of the heat transfer if the clinker is thicker than 10 cm.

Keywords