전위강하법에 의한 접지저항측정에 미치는 전류보조전극의 영향
Effects of the Current Probe on Ground Resistance Measurements Using Fall-of-Potential Method
초록
본 논문에서는 찬우
In this paper, the effects of the positions of the potential and current probes on the measurements of the ground resistance and potential gradients with the fall-of-potential method are described and the testing techniques to minimize the measuring errors are proposed. The fall-of-potential method is theoretically based on the potential and current measuring principle and the measuring error is primarily caused by the position and ground resistance of the measuring probes. The ground resistance is calculated by applying the 61.8% and rule in the fall-of-potential method, and then the potential probe is located on the straight line between the grounding electrode to be measured and the current probe. However, sometimes the grounding electrode to be measured and the measuring probes in on-site test might not be arranged on the straight line with adequate distance because there are building, road block, construction and other establishments. Provided that the grounding electrode to be measured and the measuring probes ar out of position on the straight line or have inadequate distance, the measurement of the ground resistance classically falls into an error and the measured ground resistance should be corrected. Measurements were focused on the grounding electrode system made by the ground rods of 2.4m long. It was found that the suitable separation between the grounding electrode to be measured and the current probe is more than 5 times of the length of the grounding electrode to be measured.
키워드