증발냉각시스템의 활용실태 및 냉방효과
Actual State of Practical Use and Cooling Effect of Evaporative Cooling Systems
초록
현장조사 결과 패드-팬 시스템의 경우 6개 농가 모두 사용하고 있었으며, 온실 내기온은 외부기온보다 2~5
In order to take a good look at effectiveness of cooling of Fog system and Pad-Fan system, we chose 49 farm households which were installed evaporative cooling system and 2 farm households which were installed Pad-Fan system and Fog system for a test. We execute the test on 29 households out of 49.6 households, which were installed Pad-Fan system, were able to use; however, 6 household out of 9 which were installed Fog system couldn't use it. The main reason was the clogged on nozzle. The cooling efficiency on Pad-Fan system was 77.4%, but it was very poor on Fog system. Since there are many problems on Fog system, we need more research on size of fog, the location of nozzle, control of Fog systems.