In this paper the ultimate strength of the R/C cooling towers, which have initial imperfection and pre-cracked elements, is analyzed. The initial geometric imperfections arise from the unavoidable inaccuracies under the construction and the pre-cracks are assumed to be produced by the temperature stress gradients or cyclic loading under wind pressure and/or earthquake load. Both effects are strongly influenced on the strength of the R/C cooling tower shell structures. The reinforcing ratio is also the important factor to evaluate the ultimate strength of the R/C cooling tower shells. However we could not analyze these structures experimentally because of their large, analyses are the powerful schemes to evaluate the safety and reliability of these structures. The analyzed model is Port Gibson cooling tower shell. In the numerical analysis the geometric and material nonlinearities are taken into account.

키워드

참고문헌

  1. ACI-ASCE Committee 334 (1984), "Reinforced concrete cooling tower shell - practice and commentary", ACI Journal, 81, 623-631.
  2. Hara, T., Kato, S. and Nakamura, H. (1994), "Ultimate strength of RC cooling tower shells subjected to wind load", Engineering Structures, 16(3), 171-180. https://doi.org/10.1016/0141-0296(94)90075-2
  3. Hinton, E. and Owen, D.J.R. (1984), Finite Element Software for Plates and Shells, Press, Swansea, UK.
  4. IASS Working Group 3 (1977), Recommendation for the Design of Hyperbolic or Other Similarly Shaped Cooling Towers, IASS Working Group 3, BRUSSELS.
  5. IASS The Working group on recommendations of IASS (1979), Recommendations for Reinforced Concrete Shell and Folded Plates, IASS The Working group on recommendations of IASS, MADRID.
  6. Kratzig, W.B. Gruber, K. and Zahlten, W. (1992), Numerical Collapse Simulation of Large Cooling Towers Checking Their Safety and Durability, Technical Reports Ruhr-Universitat Bochum No. 92-3.
  7. Kupfer, H. and Hilsdorf, K.H. (1969), "Behavior of concrete under biaxial stress", ACI Journal, 66(8), 656-666.
  8. Mang, H.A. and Floegl, H. (1983), "Wing-load reinforced concrete cooling towers: buckling or ultimate load?", Engineering Structures, 5(7), 163-180. https://doi.org/10.1016/0141-0296(83)90014-7
  9. Meshk, M., Mang, H.A. and Kosza, P. (1991), "Finite element analysis of cracked cooling tower shell", Journal of Structural Engineering, 117(9), 2620-2635. https://doi.org/10.1061/(ASCE)0733-9445(1991)117:9(2620)
  10. Milford, R.V. (1984), "Nonlinear behavior of reinforced concrete cooling towers", PhD thesis, University of Illinois at Urbana.
  11. Min, C.S. and Gupta, A.K. (1992), "A study of inelastic behavior of reinforced concrete shells using supercomputers", Reinforced Concreted Shell Research Report, North Carolina State University.

피인용 문헌

  1. Finite element linear and nonlinear, static and dynamic analysis of structural elements – an addendum – A bibliography (1996‐1999) vol.17, pp.3, 2000, https://doi.org/10.1108/02644400010324893
  2. Behavior of Reinforced Concrete Cooling Tower Shell under Lateral Load on Nonuniform Foundation vol.38, pp.11-12, 2017, https://doi.org/10.1080/01457632.2016.1217060