The Effective Heating Control Method of the Radiant Floor Heating System

바닥복사 난방공간의 효율적인 난방제어방법

  • 조성환 (한국에너지기술연구소 건축설비연구팀) ;
  • 태춘섭 (한국에너지기술연구소 건축설비연구팀)
  • Published : 1996.08.01

Abstract

By describing the floor slab of a radiant heating system as a one dimensional transient heat exchanger problem, a dynamic analysis model to incorperate with TRNSYS program was developed and their results were compared with experimental results. Results showed that the both of TPOC(Two Parameter On-off Control) and TPSC(Two Parameter Switching Control) method using room air temperature and floor surface temperature as the control parameters does not maintain room air and floor surface temperature exactly at the setting temperatures. But TPSC method is a better candidate for the temperature regulations of room air and floor surface temperature than TPOC method which can keep on the upper and lower limit temperature according to outside temeperature and wall structure etc. And better thermal circumstance can be given by TPSC method than On-off and TPOC method and the overheating which can be occured at the radiant floor heating system with on-off heating control will be reduced.

Keywords