The Characteristics of HVAC Noise in Office Buildings

사무소 건물의 공조설비소음 특성

  • 도영주 (한양대학교 대학원 건축공학과) ;
  • 김동규 (조선대학교 우주공학과) ;
  • 김흥식 (대한주택공사 주택연구소)
  • Published : 1989.02.01

Abstract

This study aims to provide the basic data useful in assessing indoor-noise and designing sound devices in office buildings of HVAC system. The measurements of HVAC noise were carried out in office room and mechanical room. The performance of absorptive chamber and side branch was also estimated in the office buildings which have HVAC noise problems. The results of experiments show that the NR value of indoor HVAC noise is rather higher than that of ISO recommendations at the frequencies below 500Hz. In addition, the results indicated that the absorptive chamber attenuates noise over broad band frequencies and side branch reduces noise at the special resonant frequency.

공조설비소음의 특성을 파악하기 위하여 서울의 도심에 위치한 고층 사무소 건물을 대상으로 송풍기의 파워레벨과 취출구를 통한 실내소음레벨을 측정하였다. 또한 공조설비소음이 문제시되는 건물에 흡음챔버와 사이드브랜치를 설치하여 소음기의 감음성능을 평가하였다. 연구의 결과, 실내소음레벨은 송풍기 발생소음의 영향으로 500Hz 이하의 저주파수 대역에서 ISO의 허용 기준치인 NR40을 초과하였으며 흠음챔버는 넓은 대역의 주파수, 사이드브랜치는 특정공명주파수에서 감음효과가 크게 나타났다.