한국방재학회:학술대회논문집
- 한국방재학회 2008년도 정기총회 및 학술발표대회
- /
- Pages.283-286
- /
- 2008
초기결함과 잔류응력을 고려한 345kV 송전철탑의 비선형해석
Nonlinear Analysis of 345kV Transmission Tower Considering Initial Imperfection and Residual Stress
- 발행 : 2008.02.28
초록
There were two transmission tower collapses due to Typhoon 'Maemi' in 2003. The reason that a collapse was happened was excessive wind load. One was buckled in the leg part and the other was buckled in the middle bracing part. To investigate a steel transmission tower failure mechanism, 2nd order nonlinear analysis should be performed. Considering the effect of initial imperfection and theresidual stress of angle section during nonlinear analysis, this study can estimate the ultimate strength and the ultimate behavior of the transmission tower.