Properties of Fire Resistance of High Strength Concrete Using Premixed-Cement Mixed with Synthetic Fiber

합성섬유 혼입 프리믹스시멘트 결합재를 사용한 고강도 콘크리트의 내화특성

  • 황인성 (아세아시멘트(주) 기술본부 연구개발팀) ;
  • 김성수 (아세아시멘트(주) 기술본부 연구개발팀) ;
  • 전용수 ((주)삼표 레미콘사업본부 품질팀) ;
  • 박창수 ((주)삼표 레미콘사업본부) ;
  • 한천구 (청주대 건축공학부)
  • Published : 2008.04.24

Abstract

This study investigated spalling prevention and fire resistance properties of the high strength concrete using pre-mixed cement containing fiber to prepare the method for the effective throwing of hybrid fiber. For result of a fire test, almost specimens were protected from fire except 15% of W/C. Totally, the pre-mixed cement containing fiber was favorable compared with passive mixing method for the spalling prevention. It is more effective to prevent spalling caused by fine diversion of fiber even in high strength concrete because it contained many corporate materials. Moreover, the temperature history of the side steel bar on the column test with pre-mixed cement containing fiber did not over 538$^{\circ}C$ which is the average for the standard of fire resistance performance.

본 연구에서는 폭렬방지용 합성섬유의 효과적인 투입방안 마련을 목적으로, 섬유혼입 프리믹스시멘트 결합재를 사용한 고강도 콘크리트의 폭렬방지 및 내화특성을 검토하였다. 내화시험 결과, 원주형 공시체의 폭렬은 W/C 15%의 수동투입에서 일부 박리 또는 파괴폭렬이 발생한 것을 제외하고 대부분 방지되었고, 전체적으로 섬유혼입 프리믹스시멘트는 폭렬방지 성능이 섬유 수동투입과 비교하여 동등 이상으로 우수하였으며, 결합재량이 많아 점성이 큰 고강도 콘크리트일수록 양호한 섬유의 분산성으로 폭렬방지에 더욱 효과적인 것으로 나타났다. 또한, 섬유혼입 프리믹스시멘트 결합재를 사용한 기둥부재의 온도이력은 폭렬이 방지되어 철근이 노출되지 않으면 최외곽 철근의 온도가 내화성능기준의 평균온도 538$^{\circ}C$를 넘지 않는 것으로 나타나, 고강도 콘크리트의 내화기준을 만족하였다.