Experimental Study on Heat Transfer Performance of Oil Cooler

오일 쿨러의 열전달 성능에 관한 실험적 연구

  • 조동현 (대진대학교 컴퓨터응용기계설계학과) ;
  • 임태우 (한국해양대학교 기관시스템공학부)
  • Published : 2008.11.05

Abstract

The experimental study was carried out to evaluate the heat transfer performance on the shell side of shell-and-plate finned tube heat exchanger with three different tube numbers(9, 13 and 19). Oil flowing on the shell side was cooled by cold water flowing inside the tubes. A shell-and-tube heat exchanger of an oil cooler consisted of one shell pass and two tube passes with the inner tube diameter of 8.82 mm and the tube length of 575 mm. Mass flow rate was varied from 1.2 to $6.0\;m^3/h$ for oil and from 0.6 to $3.0\;m^3/h$ for cold water, respectively. From the experiment of shell-and-plate finned tube heat exchanger, the shell side heat transfer coefficient of heat exchanger with 9 tubes was compared with that of 13 and 19 tubes. It was found that the heat exchanger with 9 plate finned tubes showed more performance of heat transfer than that of 13 and 19 tubes.

Keywords