A Study on Series Arc Detection Using Band-pass Filters

대역통과필터를 이용한 직렬아크 검출에 관한 연구

  • Published : 2008.07.16

Abstract

This paper described a method of determining whether arcing is present in a low-voltage wiring system. We simulated the series arcing that generated in electrical loads and fabricated a arc detection module which can discriminate between normal and arcing state. The module consists of a high-pass filter with a low cut-off frequency of 3 kHz to attenuate power frequency voltage and an active band-pass filter with a frequency of 4 kHz ${\sim}$ 8 kHz to detect series arc signals only. We tested an Incandescent lamp that was controlled by a dimmer and analysed. The module consists of a high-pass filter with a low cut-off frequency of 3 kHz to attenuate power frequency voltage by 80 dB and an active band-pass filter with a frequency of 4 kHz to detect series arc signals only. From the experimental results, we could detect series arc signals without an influence of non-linear loads.

Keywords