Analysis of Installation Methods of Earth Continuity Conductor on Underground Power Cable Systems

지중송전계통 병행지선 설치 방안 검토

  • Published : 2008.07.16

Abstract

In this paper, the effects of earth continuity conductor are deeply analyzed for reducing the level of induced sheath voltage at the single point bonded sections. The various installation conditions of an earth continuity conductor are considered including conductor dimensions, its spacing from the three phase cables, and utilization of two earth continuity conductors when the grounding fault occurs on real power cable systems. Finally, the transient characteristics including reduction effects of induced sheath voltage are proved by EMTP simulations. The optimal installation condition of earth continuity conductor is also proposed based on those results.

Keywords