Proceedings of the SAREK Conference (대한설비공학회:학술대회논문집)
- 2007.11a
- /
- Pages.235-240
- /
- 2007
Development of an Cross Flow Air-Cooled Plate Heat Exchanger
직교류 공랭식 판형열교환기의 성능평가
- Kim, Min-Sung (Geothermal Energy Research Center, Korea Institute of Energy Research) ;
- Lee, Jae-Hoon (Geothermal Energy Research Center, Korea Institute of Energy Research) ;
- Park, Seong-Ryong (Geothermal Energy Research Center, Korea Institute of Energy Research) ;
- Ra, Ho-Sang (Geothermal Energy Research Center, Korea Institute of Energy Research) ;
- Jeong, Jae-Hoon (Research and Development Center, LHE Co., Ltd.) ;
- Lim, Hyug (Research and Development Center, LHE Co., Ltd.)
- 김민성 (한국에너지기술연구원 지열에너지연구센터) ;
- 이재훈 (한국에너지기술연구원 지열에너지연구센터) ;
- 박성룡 (한국에너지기술연구원 지열에너지연구센터) ;
- 나호상 (한국에너지기술연구원 지열에너지연구센터) ;
- 정재훈 ((주)엘에치이 기술연구소) ;
- 임혁 ((주)엘에치이 기술연구소)
- Published : 2007.11.30
Abstract
Performance of an air-cooled plate heat exchanger (PHE) was evaluated in this study. The PHE was manufactured in two types of single-wave and double-wave plates in parallel assembly. The heat exchanger aims to substitute open-loop cooling towers with closed-loop water circulation, which guarantees cleanliness and compactness. In this study, prototype single-wave and double-wave PHEs were designed and tested in a laboratory scale experiments. From the tests, the double-wave PHE shows approximately 50% enhanced heat transfer performance compared to the single-wave PHE. However, the double-wave PHE costs 30% additional pressure drop. For the commercialization, a wide channel design for air flow would be essential for performance and reliability.
Keywords