Evaluation of Natural Ventilation Performance using the Multi-Functional Floor Heating System

다기능온돌시스템을 이용한 자연환기성능 평가

  • Cho, Dong-Woo (Division of Building & Urban Environment Research, Korea Institute of Construction Technology) ;
  • Yu, Ki-Hyung (Division of Building & Urban Environment Research, Korea Institute of Construction Technology) ;
  • Yu, Jung-Yeon (Division of Building & Urban Environment Research, Korea Institute of Construction Technology) ;
  • Jung, Hae-Kwon (Division of Building & Urban Environment Research, Korea Institute of Construction Technology)
  • 조동우 (한국건설기술연구원 건축.도시환경 연구실) ;
  • 유기형 (한국건설기술연구원 건축.도시환경 연구실) ;
  • 유정연 (한국건설기술연구원 건축.도시환경 연구실) ;
  • 정해권 (한국건설기술연구원 건축.도시환경 연구실)
  • Published : 2007.11.30

Abstract

Recently developed raised floor heating system is not only capable of basic function to reduce noise between floors, but also is a multi-functional floor heating system enabling natural ventilation. The procedure of this system for natural ventilation is to import outdoor air through bottom space of the floor heating system, circulate indoor space and discharge it out of ceiling. In winter, powerless natural ventilation is possible with buoyancy effect caused by temperature difference between outdoor and indoor. And it also allows saving of energy by importing pre-heated air in bottom space of the floor heating system. To evaluate ventilation performance of this system, on-site measurement was conducted in 2 test laboratories, and the nominal air change rate was satisfied as 0.4$\sim$0.8 h-1 under the condition of outdoor temperature $5^{\circ}C{\sim}-5^{\circ}C$, which was evaluated as highly possible to be applied as a natural ventilation system in multi-family houses.