Performance Analysis of a Centrifugal Compressor for HFC-134a with Variation of Diffuser Vane Angle

디퓨저 베인 설치각 변화에 따른 R134a 원심압축기 성능 분석

  • Published : 2007.05.30

Abstract

Numerical simulation on the two-stage centrifugal compressor with Low Solidity Vaned Diffuser LSVD) for HFC-134a Turbo-chiller was performed using a commercial code. The comparative study with experimental results from other compressor was also investigated to testify the simulation schemes. The numerical analysis was separately simulated for each stage of the compressor and the effect of impeller-diffuser flow interaction was considered. Setting angle of the diffuser vane changed in the range of 15 deg. and the effects on its variation were discussed in detail including the flow analysis in the passage of the compressor. The vane setting angle obtained from the preliminary design was slightly adjusted to the optimal value by the performance enhancement in terms of pressure recovery and flow characteristics.