Experimental measurements of R-22 two-phase friction factor in plate heat exchangers

판형열교환기에서 R-22 냉매의 이상 압력 손실계수 평가

  • Published : 2007.05.30

Abstract

Brazed Plate Heat Exchanger (BPHE) is a type of compact plate heat exchanger with parallel corrugated plates which are brazed together in series. Each plate hascorrugation called herringbone pattern. Inside a BPHE, hot fluid and cold fluid alternate its flow direction to establish counter current flow configuration. Two-phase flow heat transfer and pressure drop of R-22 in BPHE were experimentally measured in this study. In the present experiments, single-phase region and two-phase region coexist in a BPHE. Therefore, the inside of a BPHE have to be divided into single phase region and two phase region and analyzed accordingly. The results from the single phase flow analysis are then extended to the two phase flow analysis to correlate the condensation and evaporation heat transfer and pressure drop for the refrigerant R-22 in the BPHEs. Previous models for two- phase friction factor have been compared with the present experimental results.

Keywords