Considerations in Down-conductor System and Earth-termination System Design of Apartments

공동주택에서의 인하도선시스템과 접지시스템 설계에 대한 고찰

  • Published : 2006.05.11

Abstract

This paper deals with primary consideration in down-conductor system and earth-termination system design of apartments. For down-conductor system, steelworks within reinforced concrete apartment structures have the electrical continuity, however, lashing is not suitable for lightning-current-carrying connections. So this paper suggest that the additional dedicated conductors should be installed and they are should be lashed to the reinforcement steel. Also this paper suggested the foundation earth electrode and global earth system as the earth-termination system of the apartments. But perfect bonding system is essential in lightning protection system to avoid life hazard and to protect electronic equipments.

본 논문에서는 공동주택에 적합한 인하도선시스템과 접지시스템 설계를 위한 기본적 사항에 대하여 고찰하였다. 공동주택의 철근구조체는 전기적 연속성을 갖지만 철근들끼리의 결속선에 의한 접속은 전자기계력에 대한 내력이 부족하다. 따라서 전용의 인하도선을 설치하고 이들을 건물 양 측벽의 철근구조체와 본딩하여 낙뢰전류가 인하도선 및 철근구조체에 분산되어 흐르게 하는 인하도선시스템을 제시하였다. 한편 공동주택의 접지시스템은 건물기초접지극과 피뢰설비를 위한 환형 접지극으로 각각 구성하고 이들을 서로 본딩하는 접지시스템을 제시하였다. 또한 공동주택 각동의 건물기초접지극을 공동구의 철근구조체나 접지선을 이용하여 서로 연결함으로서 공동주택 단지에 거대한 총괄접지시스템을 구현하는 방안을 제시하였다. 하지만 이러한 피뢰시스템을 구축하기 위해서는 완벽한 본딩시스템의 구축이 전제되어야 한다.