Verification Experiment and Simulation of Cooling Load for a Test Space with Forced Ventilation

시험공간에 강제환기를 고려한 냉방부하의 실증실험 및 시뮬레이션

  • 김동혁 (경희대학교 대학원 기계공학과) ;
  • 유호선 (숭실대학교 기계공학과) ;
  • 홍희기 (경희대학교 기계산업시스템공학부)
  • Published : 2005.11.25

Abstract

Building energy consumption according to the ventilation has been considered to be an important subject. The purpose of this study is to investigate the cooling loads in a test space with a forced ventilating system. In the test space, on/off controlled air-conditioning and forced ventilating facility were operated between 8:30 to 21:00 during 4 days and some important data like temperatures and energy consumption were measured to obtain actual cooling loads. The simulation was carried out in a mode of temperature level control using a TRNSYS 15.3 with a precisely measured air change amount and performance data of air-conditioner. Cooling loads including sensible and latent were compared between by experiment and by simulation. Both of cooling loads associated with ventilation show a close agreement within an engineering tolerance.