A Study on the Design and Analysis of District Solar Heating and Cooling System with Preheating of Returning District Heating Water

지역난방수 환수 승온방식의 태양열 지역냉난방 시스템 분석

  • Published : 2005.06.01

Abstract

This study was carried out the design and analysis of solar thermal system with preheating of returning district heating water for the Chung-ju district heating and cooling system. Two different types of solar collectors are used for this system. TRNSYS simulation program was used for the analysis. As a results, the solar system efficiency is $35.8\%$ for the plate type and $45.1\%$ for the evacuated type solar collector in the case of $50^{\circ}C$ for the returning district heating water temperature. The returning district heating water temperature is on of the very important factors that is influence on the system efficiency. So the effect of the returning district heating water temperature on the system efficiency is analyzed in this study.

Keywords