Heat Exchange Charaterictics of Water under the Low Pressure by driving Ejector

에젝터 구동 저압 증발하에서 물의 열교환 특성

  • 신유식 (경상대학교 대학원 정밀기계공학과) ;
  • 이윤환 (경상대학교 대학원 정밀기계공학과) ;
  • 이상철 (경상대학교 대학원 정밀기계공학과) ;
  • 김세현 (경상대학교 대학원 정밀기계공학과) ;
  • 정효민 (경상대학교 기계항공공학부 해양산업연구소) ;
  • 정한식 (경상대학교 기계항공공학부 해양산업연구소)
  • Published : 2003.04.23

Abstract

The cooling tower is a device for making a cooling water in the air conditioning system of building, and there are many kinds of cooling tower system for air conditioner. In this paper, we introduced the water cooling system with an enclosed tank and water ejecting system for evaporating the water in tank. The city water was used for a working fluid, and the cooling water is generated by evaporating latent heat in the tank with a $25{\sim}50mmHg$. The time to reaching this vacuum pressure was about $20{\sim}30minutes$, and cooling water was obtained the value of temperature difference ${\Delta}T=7^{\circ}C$.

Keywords