Chararcteristics of Water Vapor Transmission in Base Resin for Underground Residential Distribution Power Cable

지중배전케이블 기저수지의 수증기 투과 전달특성

  • Published : 2003.05.16

Abstract

In URD(Underground Residential Distribution) power cable, experiments of WVT(Water Vapor Transmission) test on the Base Resin accomplished to specimens which contained CB(Carbon Black), anti-oxidant to base resin and made by pressing to resin of pellet or lump form. a kind of specimens was HDPE(High Density Polyethylene), MDPE(Medium Density Polyethylene), LDPE(Low Density Polyethylene), LLDPE(Linear Low Density Polyethylene), PVC(Polyvinyl Chloride). as a results of WVT test, we saw that WVT ratio was HDPE < LLDPE < MDPE≒LDPE${\ll}$ PVC. WVT properties of PVC using for jacket showed properties 15-20 times more than MDPE or LLDPE. Therefore, to development of watertightness cable, our works present need of Changing in insulating materials.

Keywords