Flexible pipes (corrugated polyethylene pipes) are normally used for underground power distribution grids. In this paper, dynamic analysis was carried out through FEM in order to investigate the structural behaviour of pipes subjected to seismic loads. The burial depth and the number of pipes were major parameters in the numerical analysis to determine the response of pipes. The results show that the displacement of pipes under given conditions are all satisfactory in comparison of the allowable strain criteria -maximum 3.5 %.