Proceedings of the KSME Conference (대한기계학회:학술대회논문집)
- 2002.08a
- /
- Pages.737-738
- /
- 2002
CFD Analysis of Gas Insulated Switchgear with Moving Grid
이동격자를 이용한 초고압 차단기 유동해석
Abstract
To develop and improve a GIS(Gas Insulated Switchgear), the prediction of the pressure in puffer cylinder and the flow between the nozzle and the moving electrode within GIS is very important.The leading companies in GIS business issue the results of the study of flow within GIS including arc plasma. In this study, the characteristics of the flow of the GIS developed by HHI(Hyundai Heavy Industries Co. Ltd.) was investigated. To simulate the compressible flow of GIS, the CFX, a commercial CFD code, was used. With moving grid method, the movement of piston and electrode was simulated. The moving grid method was superior to the method of varying the property of cells to move an obsticle, in stability and convergencce of solution. The calculated maximum pressure within the puffer cylinder was matched with experimental data within