The comparison between Numerical Computation and Experiment on Fluid Elow in Rectangular Duct

사각덕트내의 유체유동에 관한 수치계산과 실험의 비교

  • Published : 2002.08.01

Abstract

Fluid flow in a rectangular duct system are measured by W laser doppler velocity meter, and also computed by commercial software of STAR-CD for comparison between then First, for a rectangular duct with 90 degree metered elbow, the fluid flow with Reynolds numbs's of 1,508 is predicted by assumption of both laminar and turbulent models. But, even though the Reynolds number is less than 2,300-3,000, the computation by turbulent model is close to the experimental data. Moeover, the computation by turbulent model for Reynolds number of 11,751 also predicts the experimental data satisfactorily. Second, for a rectangular duct with two branch ducts, the ratios between flow rates in the two branches are invariant to Reynolds number according to both of numerical and experimental results.

Keywords