Proceedings of the KIPE Conference (전력전자학회:학술대회논문집)
- 2002.07a
- /
- Pages.555-558
- /
- 2002
A Study on the Islanding Detection for Grid Connected Photovoltaic System
계통연계형 태양광발전시스템을 위한 단독운전 검출에 관한 연구
- Lee Gi-Je (SAMWHA Engineering Co., Ltd.) ;
- Kim Min (SAMWHA Engineering Co., Ltd.) ;
- Lee Jin-Seop (SAMWHA Engineering Co., Ltd.) ;
- Yu Gwon-Jong (KIER)
- Published : 2002.07.01
Abstract
The general ways of the anti-islanding can be classified into the active method and passive method. The passive method which use only the voltage information when power failure occurs has much possibility of the wrong detection. And the active method detects the change of the voltage frequency as instantaneously changing the frequency of the inverter output current. Therefore, in this paper, the method to inject arbitrary order harmonics into controlled current is proposed. In this method islanding can be detected by measuring the amount of load voltage of injected harmonics order. And as a current control method predictive control method is used, which make actual current accurately to track reference current by Instantaneously computing converter output voltage and has fast response in transient state. This parer proposed method was verified by simulation.
Keywords