A Pollution Cycle Method to Evaluate the Electrical Properties of Outdoor Insulators

옥외 절연물의 전기적 특성 평가를 위한 오손주기시험법

  • Published : 2001.05.11

Abstract

In this research, a experiment was performed to evaluate the electrical properties of outdoor insulator with the pollution cycle method. Cycle test methods such as DCM of STRI, IEC 61109 compared with pollution cycle method. Using dimatic properties of Korea peninsula, we could get the optimal condition for the pollution cycle method. As the factor, clean and saline fog, voltage, rainfall and drying was chosen. The applied voltage is 13,2 kV, the salinity of salt solution was changed from 0.1 wt% to 1.5 wt% and one cycle is about 4 hours. To ensure the reproducibility and reliability, experiments repeated 4 times. The leakage current was measured with Lab VIEW and the ESDD was measured with brushwiping method. This experiment could ensure superiority of pollution cycle method which developed through the result of this experiment and we could know the relationship between ESDD, leakage current and relative humidity.