The simulation on the characteristics of ventilation in the subway platform

지하철 승가장내의 환기 특성에 관한 해석적 연구

  • Published : 2001.06.27

Abstract

The purpose of present study is to find design parameters and operating conditions of the HVAC system in a subway platform. The simulation was carried out for the flow, heat and mass transfer for heating, ventilating and air-conditioning(HVAC) environments in the subway platform. The steady-state. incompressible flow assumption and standard $k-{\varepsilon}$ turbulence model are adopted. The location of HVAC air inlet above platform and the volume flow rate of curtain air released from inlet B are chosen as main parameters in this study. The results of present study are following: In the case of existence of train, the heat and contaminant released under the train have no effect on the average temperature and mass fraction of contaminant in the platform, but heat released on the train has influence on the average temperature in the platform. Train acts as an obstacle to exhaust the contaminant in the platform, but has good effect on the average temperature in the platform.