Approximate Optimum Thermal Design Analysis of Combined Cycle Power Plant

복합화력 발전플랜트의 근사 최적 열설계 해석

  • 전용준 (현대건설(주) 기술연구소) ;
  • 신흥태 (현대건설(주) 기술연구소) ;
  • 이봉렬 (서울대학교 대학원 기계공학부) ;
  • 김동섭 (인하대학교 기계공학과) ;
  • 노승탁 (서울대학교 기계항공공학부)
  • Published : 2001.11.01

Abstract

An optimum thermal design analysis of the combined cycle power plant with triple pressure heat recovery steam generator was performed by the numerical simulation. The optimum design module used in the paper is DNCONF, a function of IMSL Library, which is widly known as a method to search for the local optimum. The objective function to be minimized is the cost of total power plant including the steam turbine power enhancement premium. The result of this paper shows that the cost reduces if the design point of power plant becomes the local optimum, and many calculations at various initial conditions should be carried out to get the value near the global optimum.

Keywords