Internal Model Control of UPS Inverter using Resonance Model

  • Park J. H. (Tongmyong College) ;
  • Kim D. W. (Tongmyong College) ;
  • Kim J. K. (Pukyong National University) ;
  • Lee H. W. (Kyungnam University) ;
  • Noh T. K. (Donga University) ;
  • Woo J. I. (Donga University)
  • 발행 : 2001.10.01

초록

In this paper, a new fully digital control method for single-phase UPS inverter, which is based on the double control loop such as the outer voltage control loop and inner current control loop, is proposed. The inner current control loop is designed and implemented in the form of internal model control and takes the presence of computational time-delay into account. Therefore, this method provides an overshoot-free reference-to-output response. In the proposed scheme, the outer voltage control loop employing P controller with resonance model implemented by a DSP is introduced. The proposed resonance model has an infinite gain at resonant frequency, and it exhibits a function similar to an integrator for AC component. Thus the outer voltage control loop causes no steady state error as regard to both magnitude and phase. The effectiveness of the proposed control system has been demonstrated by the simulation and experimental results respectively.

키워드