불용성 오손물에 의한 절연물의 전기적 특성에 관한 연구

The Electric Properties of Insulators Due to Non-soluble Contaminant

  • 발행 : 2000.07.01

초록

This paper present the result of the investigation, the electric properties of insulators due to non-soluble contamination. In general, the humidity and the amount of soluble salts such as NaCl, MgCl$_2$are the most dominant factor. Though the non-soluble do not distribute on conductivity of contaminant layer, that has the hygroscopic property. For this study, we make a mini-fog chamber with transparent acryl and the kaoline was used for non-soluble contaminant. The kaoline was applied with sprayer to get the specific ESDD and NSDD value, then the specimen was dried and installed horizontally. And to measure the leakage current a DAS system was developed with LabView. With the result, we could know the influence of non-soluble content and the relationship between NSDD and ESDD.

키워드