A Study on the Composition Variation of 600v IV with Thermal Deterioration

열열화에에 따른 600V IV의 조성변화에 관한 연구

  • 최충석 (한국전기안전공사 전기안전시험연구원) ;
  • 류선희 (한국전기안전공사 전기안전시험연구원) ;
  • 김형래 (한국전기안전공사 전기안전시험연구원) ;
  • 이경섭 (동신대학교 전기전자공학과)
  • Published : 1999.05.01

Abstract

The weight decreases of the thermal deteriorated IV were rapidly increased at 80$0^{\circ}C$ and over. At the results of the analysis of the metallurgical microscope photographs. the surface of the thermal deteriorated IV at 30$0^{\circ}C$ was mixed with the elongated and original structures of Cu. But the elongated structures could not detected at 90$0^{\circ}C$ and over. The surface structures of SEM were detected a lot of small rounded particles between crystallizations. The EDX spectra of the thermal deteriorated IV at 3$0^{\circ}C$ were uniformly detected CuL, CuK, OK, and CIK, regardless of the scanning length, but the spectra of CIK could not found at 90$0^{\circ}C$. At the DTA curves, the endothermic reactions were occurred at about 25$0^{\circ}C$ to 30$0^{\circ}C$ and 43$0^{\circ}C$, and the exothermic reactions were occurred at about 48$0^{\circ}C$ respectively.

Keywords