Operating properties of the resistive and inductive SFCL with the three-phase fault

3상 단락사고에 대한 저항형과 유도형 한류기의 동작특성

  • 최효상 (한전 전력연구원 전력계통연구실) ;
  • 현옥배 (한전 전력연구원 전력계통연구실) ;
  • 김상준 (한전 전력연구원 전력계통연구실)
  • Published : 1999.11.01

Abstract

We studied the operating properties of resistive and inductive SFCLS with 100 $\Omega$ of quench impedance for a three-phase-fault in the 154 kV transmission system. The fault simulation at the phase angles 0$^{\circ}$ , 45$^{\circ}$ , and 90$^{\circ}$ showed that the resistive SFCL limited the fault current less than 16 kA without any DC component after one half cycle from the instant of the fault. On the other hand, the inductive SFCL suppressed the current below 11 kA, but with 3-4 kA of DC component which decreased to zero in 5 cycles. We concluded that the inductive SFCL had higher performance in current limiting but the resistive SFCL was better from the view point of DC components.