Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 1998.11a
- /
- Pages.88-90
- /
- 1998
Eddy Current Analysis In Cover Plate of Power Transformers using Indirect Boundary Integral Equation Method
간접경계적분법을 이용한 변압기 cover plate에서의 와전류 해석
- Kim, Sang-Young (School of Electrical Engineering, Seoul National University) ;
- Kim, Dong-Hun (School of Electrical Engineering, Seoul National University) ;
- Han, Song-Yop (School of Electrical Engineering, Seoul National University)
- Published : 1998.11.28
Abstract
In this paper, the indirect BIEM(boundary integral equation method) is adopted to analyze 3-D eddy currents in cover plate of power transformer. In indirect BIEM, the equivalent magnetic surface charge density and the eqivalent magnanetic surface current density are the unknowns. Using triangular constant elements, the integral equations are discretized into boundary element equations of minimum order. Eddy currents are obtained in terms of euqivalent magnetic surface sources. And the locad overheating can be predicted using the eddy currents distribution in cover plate of power transformer.
Keywords