Statistical Analysis of Breakdown Voltage using needle electrode inserted in XLPE

침전극하에서 XLPE의 절연파괴강도의 통계적평가

  • Published : 1998.11.28

Abstract

The needle electrode was inserted in virgin and 1.000 hr aged XLPE which is the insulation used for 22.9 kV underground distribution cable with the distance of 1, 1.5 and 2mm respectively. Breakdown voltage were measured for the virgin and 1.000 hr aged specimen and statistically evaluated through Weibull distribution. As the of electrode increase in virgin and 1.000 hr aged specimen. shape parameter and scale parameter showed increase coincidently. For shape parameter, the value of aged specimen showed the higher than that of virgin specimen.

Keywords